| Model | ENC-AR310LE | ENC-AR320LE |
| Type | Non-drain Lateral-mount type | |
| Cooling scheme | Compressor | |
| Cooling capacity (W) | 280/300 (50/60Hz) | |
| Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
| Current consumption (A)(MAX) | 3.7/3.8 | 2.1/1.9 |
| Starting current (A) | 7.4/7.7 | 4.0/4.2 |
| Power consumption (W)(MAX) | 340/370 | 360/355 |
| Allowable ambient temperature (ºC) | 20 to 50 | |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
| Refrigerant | R-134a (A kind of freon that is not prohibited) | |
| Temperature setting range (ºC) | 25 to 45 | |
| Number of fans | 2 | |
| Output | Output of operation & alarm(250V 2A) | |
| Display | LED Temperature/Error RUN | |
| Noise immunity | Level 4 in the fast transient/Burst immunity test | |
| Noise (dB) | Approx. 59/63 | |
| Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm | |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige | |
| Outer dimensions (mm) | H590×W200×D250 | |
| Weight(kg) | 18 | |

| Model | ENC-AR510LE | ENC-AR520LE |
| Type | Non-drain Lateral-mount type | |
| Cooling scheme | Compressor | |
| Cooling capacity (W) | 400/500 (50/60Hz) | |
| Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
| Current consumption (A)(MAX) | 3.6/3.7 | 1.9/1.6 |
| Starting current (A) | 7.4/7.7 | 4.0/4.2 |
| Power consumption (W)(MAX) | 320/360 | 330/300 |
| Allowable ambient temperature (ºC) | 20 to 50 | |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
| Refrigerant | R-134a (A kind of freon that is not prohibited) | |
| Temperature setting range (ºC) | 25 to 45 | |
| Number of fans | 2 | |
| Output | Output of operation & alarm(250V 2A) | |
| Display | LED Temperature/Error RUN | |
| Noise immunity | Level 4 in the fast transient/Burst immunity test | |
| Noise (dB) | Approx. 63/67 | |
| Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm | |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige | |
| Outer dimensions (mm) | H500×W350×D230 | |
| Weight(kg) | 19 | |

| Model | ENC-AR810LE | ENC-AR820LE |
| Type | Non-drain Lateral-mount type | |
| Cooling scheme | Compressor | |
| Cooling capacity (W) | 700/800 (50/60Hz) | |
| Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
| Current consumption (A)(MAX) | 6.5/6.4 | 3.2/3.2 |
| Starting current (A) | 15.6/14.7 | 7.5/7.1 |
| Power consumption (W)(MAX) | 590/630 | 600/610 |
| Allowable ambient temperature (ºC) | 20 to 50 | |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
| Refrigerant | R-134a (A kind of freon that is not prohibited) | |
| Temperature setting range (ºC) | 25 to 45 | |
| Number of fans | 2 | |
| Output | Output of operation & alarm(250V 2A) | |
| Display | LED Temperature/Error RUN | |
| Noise immunity | Level 4 in the fast transient/Burst immunity test | |
| Noise (dB) | Approx. 64/68 | |
| Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm | |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige | |
| Outer dimensions (mm) | H730×W300×D280 | |
| Weight(kg) | 26 | |

| Model | ENC-AR1310LE |
| Type | Non-drain Lateral-mount Type |
| Cooling scheme | Compressor |
| Cooling capacity (W) | 1150/1300(50/60Hz) |
| Power supply (50/60Hz) | 1 phase 100VAC±10% |
| Current consumption (A)(MAX) | 8.6/9.0 |
| Starting current (A) | 22.3/20.5 |
| Power consumption (W)(MAX) | 770/870 |
| Allowable ambient temperature (ºC) | 20 to 55 |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) |
| Refrigerant | R-407c |
| Temperature setting range (ºC) | 25 to 45 |
| Number of fans | 3 |
| Output | Output of operation & alarm(250V 2A) |
| Display | LED Temperature/Error RUN |
| Noise immunity | Level 4 in the fast transient/Burst immunity test |
| Noise (dB) | Approx. 68/72 |
| Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige |
| Outer dimensions (mm) | H900×W400×D251 |
| Weight(kg) | 36 |

| Model | ENC-AR1320LE |
| Type | Non-drain Lateral-mount Type |
| Cooling scheme | Compressor |
| Cooling capacity (W) | 1150/1300 (50/60Hz) |
| Power supply (50/60Hz) | 1 phase 200V±10% |
| Current consumption (A)(MAX) | 4.2/4.4 |
| Starting current (A) | 12.7/11.6 |
| Power consumption (W)(MAX) | 805/880 |
| Allowable ambient temperature (ºC) | 20 to 50 |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) |
| Refrigerant | R-407c |
| Temperature setting range (ºC) | 25 to 45 |
| Number of fans | 3 |
| Output | Output of operation & alarm(250V 2A) |
| Display | LED Temperature/Error RUN |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige |
| Outer dimensions (mm) | H900×W400×D251 |
| Weight(kg) | 36 |

| Model | ENC-AR2400LE |
| Type | Non-drain Lateral-mount Type |
| Cooling scheme | Compressor |
| Cooling capacity (W) | 2100/2400(50/60Hz) |
| Power supply (50/60Hz) | 3 phase 200VAC±10% |
| Current consumption (A)(MAX) | 5.0/4.6 |
| Starting current (A) | 31/30 |
| Power consumption (W)(MAX) | 1490/1770 |
| Allowable ambient temperature (ºC) | 20 to 55 |
| Allowable ambient humidity (%) | 10 to 85 (No condensation) |
| Refrigerant | R-134a |
| Temperature setting range (ºC) | 25 to 45 |
| Number of fans | 5 |
| Output | Output of operation & alarm(250V 2A) |
| Display | LED Temperature/Error RUN |
| Noise immunity | Level 4 in the fast transient/Burst immunity test |
| Noise (dB) | Approx. 70/73 |
| Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm |
| Paint color | Munsell 5Y7/1 Equivalent color of light beige |
| Outer dimensions (mm) | H1380×W450×D230 |
| Weight(kg) | 63 |